P/N

SFS-NV82.5

FEATURES

  • Pneumatic or manually activation
  • Safety pin included
  • Automatically reset

DESCRIPTION
Needle valve SFS-NV82.5 is used for trigger FM-200 cylinder 82.5L discharge. The needle valve SFS-NV82.5 will be installed on FM-200 cylinder actuation port. Pressurized actuation gas from the pilot cylinder is used to actuate the needle valve through copper tube / flexible actuation hose. The needle valve SFS-NV82.5 is equipped with a PUSH button that is used for manually actuation incase pilot system fail or operation by person.

INSTALLATION
The needle valve should be installed to FM-200 cylinder actuation port only when system has completed test and commissioning. The FM-200 cylinder discharge port has connected to system piping and cylinder has secured in place.

Never install needle valve to FM-200 cylinder with discharge port open. Fail to do this can make the incident discharge lead to not safe for person a rounding.